Selec DIN RAIL MOUNT 240W,o/p 24 volt 10 ampere. POWER SUPPLY Product: RPS240
₹2,444.00
RPS240 DIN Rail Mount Power Supply, a robust and efficient solution designed to deliver reliable power with precision.
Operating with an input voltage range of 90 – 264 VAC (127 – 370 VDC) and at a frequency of 50/60 Hz, this power supply is adaptable to various power setups.
The inrush current, measured at 264 VAC and 25°C ambient temperature during cold start, is below 48 Amps, ensuring smooth power-up sequences.
With an output voltage of 24 volts and a current of 10 amperes, this power supply provides a solid output performance of 240 watts.
Voltage tolerance is kept within a tight ± 1% range, ensuring consistent and reliable power delivery.
Line regulation remains below 1% of the output voltage, while load regulation is maintained at ± 1%, reflecting the power supply’s high level of stability.
The power supply’s turn-on time is swift, less than 1 second at 230 VAC and less than 3 seconds at 115 VAC with full load.
With a hold-up time of ≥60ms at 230V AC and ≥15ms at 115V AC under full load, this power supply ensures smooth operation during power fluctuations.
Its compact dimensions of 50 x 136 x 135 mm (W x H x D) make it suitable for DIN rail mounting, a practical and space-efficient choice.
Operating within a temperature range of -25°C to +70°C, the power supply ensures reliability even in demanding environments.
Certified for CE approval, this power supply meets high standards of quality and safety.
- Description
- Additional information
Description
Input Voltage | 90 – 264 VAC (127 – 370 VDC) |
Input Frequency | 50/60 Hz |
Inrush Current | < 48 Amps; Measured at 264 VAC, 25°C Ambient, Cold start |
Output Voltage | 24 volt 10 ampere |
Output Power | 240 W |
Voltage Tolerance | ± 1 % |
Line Regulation | < 1% of Vout |
Load Regulation | ± 1 % |
Turn On Time | < 1 sec @ 230 VAC & < 3 sec @ 115 VAC, Full load |
Hold Up Time | ≥60ms at 230V AC & ≥15ms at 115V AC, Full load |
Rise Time | < 100 ms |
Overload Protection | > 110% of rated output current; Hiccup type; Autorecovery |
Overvoltage Protection | Latched type; Input AC power to be recycled to recover the power supply |
Output Short Circuit Protection | Hiccup mode when output is shorted; Autorecovery type |
Operating Temperature | – 25°C to + 70°C; De-rate linearly above 50°C from 100 % load at 50°C to 50 % load at 70°C,- 25°C to 0°C start-up is guaranteed with specification deviation |
Storage Temperature | – 40°C to + 85°C |
Cooling | Natural convection cooled |
Humidity | 5 to 95 % RH, Non condensing |
Altitude | 2000 m |
Dimension | 50 x 136 x 135 mm (W x H x D) |
Weight | 645 gms |
Mounting | 35 mm Din rail |
Additional information
Weight | 2 kg |
---|