Selec DIN RAIL MOUNT 240W,o/p 24 volt 10 ampere. POWER SUPPLY Product: RPS240

2,444.00

RPS240 DIN Rail Mount Power Supply, a robust and efficient solution designed to deliver reliable power with precision.

Operating with an input voltage range of 90 – 264 VAC (127 – 370 VDC) and at a frequency of 50/60 Hz, this power supply is adaptable to various power setups.

The inrush current, measured at 264 VAC and 25°C ambient temperature during cold start, is below 48 Amps, ensuring smooth power-up sequences.

With an output voltage of 24 volts and a current of 10 amperes, this power supply provides a solid output performance of 240 watts.

Voltage tolerance is kept within a tight ± 1% range, ensuring consistent and reliable power delivery.

Line regulation remains below 1% of the output voltage, while load regulation is maintained at ± 1%, reflecting the power supply’s high level of stability.

The power supply’s turn-on time is swift, less than 1 second at 230 VAC and less than 3 seconds at 115 VAC with full load.

With a hold-up time of ≥60ms at 230V AC and ≥15ms at 115V AC under full load, this power supply ensures smooth operation during power fluctuations.

Its compact dimensions of 50 x 136 x 135 mm (W x H x D) make it suitable for DIN rail mounting, a practical and space-efficient choice.

Operating within a temperature range of -25°C to +70°C, the power supply ensures reliability even in demanding environments.

Certified for CE approval, this power supply meets high standards of quality and safety.

Category:

Description

Input Voltage 90 – 264 VAC (127 – 370 VDC)
Input Frequency 50/60 Hz
Inrush Current < 48 Amps; Measured at 264 VAC, 25°C Ambient, Cold start
Output Voltage 24 volt 10 ampere
Output Power 240 W
Voltage Tolerance ± 1 %
Line Regulation < 1% of Vout
Load Regulation ± 1 %
Turn On Time < 1 sec @ 230 VAC & < 3 sec @ 115 VAC, Full load
Hold Up Time ≥60ms at 230V AC & ≥15ms at 115V AC, Full load
Rise Time < 100 ms
Overload Protection > 110% of rated output current; Hiccup type; Autorecovery
Overvoltage Protection Latched type; Input AC power to be recycled to recover the power supply
Output Short Circuit Protection Hiccup mode when output is shorted; Autorecovery type
Operating Temperature – 25°C to + 70°C; De-rate linearly above 50°C from 100 % load at 50°C to 50 % load at 70°C,- 25°C to 0°C start-up is guaranteed with specification deviation
Storage Temperature – 40°C to + 85°C
Cooling Natural convection cooled
Humidity 5 to 95 % RH, Non condensing
Altitude 2000 m
Dimension 50 x 136 x 135 mm (W x H x D)
Weight 645 gms
Mounting 35 mm Din rail

Additional information

Weight 2 kg